Home > PRODUCTS > Smart Switchgear Series > GLSV-ZNH5-40.5
GLSV-ZNH5-40.5
Smart Phase Controlled Circuit Breaker

GLSV-ZNH5-40.5 is an smart phase controlled circuit breaker designed specifically for 40.5 kV nonlinear load applications. It supports phase-selective switching, non-full-phase operation, and anti-pumping control, significantly reducing inrush current and system transients during closing.

The device adopts three-phase independent operation with a permanent magnet mechanism, enabling high-precision switching control with ±0.5 ms accuracy. An integrated energy storage module ensures low-power operation, and the unit features online monitoring, event recording, and operation waveform capture.

With a compact structure and mechanical lifespan ≥30,000 operations, it also supports manual emergency tripping. It is ideally suited for precision control of critical loads such as transformers, capacitor banks, and reactors.


Main Functions
  • (1)
    Phase-Controlled Switching for Nonlinear Loads
  • (2)
    Non-Full-Phase Operation Capability
  • (3)
    Anti-Pumping Function
  • (4)
    Event Logging Function
  • (5)
    Operation Waveform Recording
  • (6)
    Online Monitoring of Closing/Opening Coil Circuit Integrity
  • (7)
    Manual Mechanical Trip Capability
KEY Features
  • 1
    Phase-Selective Switching
    Enables any switching strategy through separate phase control using a permanent magnet operating mechanism
  • 2
    High Precision Timing
    Ensures consistent operation with action time dispersion within ±0.5 ms under all conditions
  • 3
    Robust Mechanics
    Robust mechanical design with a lifespan of no less than 30,000 operations
  • 4
    Manual Trip Capability
    Supports mechanical manual trip operation regardless of power status
  • 5
    Low Power Operation
    Operates with external power current under 0.5 A, ensuring low energy consumption during operation
SPECIFICATIONS
  • Rated Voltage
    40.5kV
  • Rated Current
    630 A, 1250 A, 1600 A, 2000 A, 2500 A, 3150 A, 4000 A
  • Rated Short-Circuit Breaking Current
    20 kA, 25 kA, 31.5 kA, 40 kA
  • Closing/Opening Control Voltage
    220 V DC/AC
  • Opening/Closing Time Deviation
    Within ±0.5 ms
  • Mechanical Endurance
    M2
  • Electrical Endurance
    E2