SID-2SL-A(B)
Multi-Function Synchroscope

The SID-2SL-A(B) Multi-Function Synchroscope is a high-performance microprocessor-based synchronization instrument supporting up to 16 synchronization points. It features both manual and automatic synchronizing interlocking functions, providing fourfold interlock protection based on voltage difference, frequency difference, phase angle difference, and power angle, ensuring safe and reliable grid connection.

The device supports real-time display of system-side and incoming-side voltage and frequency, as well as various differential parameters, and provides multiple sets of independent high-capacity interlocking outputs.

Equipped with automatic phase-angle compensation, self-diagnostics, and dead-voltage closing interlock, the SID-2SL-A(B) adopts a user-friendly bilingual (Chinese/English) interface. It is widely applicable to synchronization monitoring scenarios with multiple connection points in power plants and substations.

Main Functions
  • (1)
    Single-side or dual-side dead-voltage closing interlock
  • (2)
    Automatic phase-angle compensation to offset inherent phase differences between two synchronization voltages
  • (3)
    Hardware-based real-time self-diagnostics
  • (4)
    Automatic synchronization interlocking
  • (5)
    Manual synchronization interlocking
  • (6)
    Supports 1 to 16 synchronization points with freely configurable grid-connection attributes
KEY Features
  • 1
    Fourfold Synchronization Interlocking Protection
    Provides fourfold interlocking based on voltage difference, frequency difference, phase angle difference, and power angle, ensuring safe synchronization and grid connection.
  • 2
    Real-Time Measurement and Display
    Supports real-time display of system-side and incoming-side voltage and frequency, as well as measurement values including voltage difference, frequency difference, and phase angle difference.
  • 3
    Independent High-Capacity Interlocking Outputs
    Offers independent high-capacity synchronization interlocking contacts for the closing circuits of up to 16 synchronization points.
  • 4
    Bilingual User Interface
    Features a user-friendly human–machine interface (HMI) with support for both Chinese and English.
SPECIFICATIONS
  • Rated Frequency
    50Hz or 60Hz
  • PT Rated Voltage
    220V or 100V or 57.7V
  • Digital Input Rated Voltage
    110V or 220V DC
  • Output Relay
    Dry contact (potential-free)
  • Operating Temperature
    –20 °C to +55 °C
  • Storage Temperature
    –20 °C to +80 °C